Data-centre cooling with RL — how the 40% figure was earned

Google's DeepMind reported a 40% cut in cooling energy at their data centres. The number is real. The tool that delivered it was not reinforcement learning turning valves — it was a learned optimiser choosing setpoints, running advisory-first, with hard safety constraints and operator override. This is what that looks like.

The plant · IT load 1 MW

WET-BULB 15.0 °C IT HALL INLET 22.0 °C CHILLER C CHILLER 285 kW COOLING TOWER FAN 31 kW CHW 7 °C RETURN FREE-COOLING BYPASS POLICY : BASELINE SAFETY CLAMP
Hour 0 / 168 · Mon
Baseline kWh
0
Smart kWh
0
Reduction
%
Smart PUE
CHW setpoint
7.0 °C
Fan speed
80 %
Mode
CHILLED